주방후드와 화장실배기 가동시 대상세대 환기량 측정
홍구표, 박철용, 임성재 · 대한설비공학회 동계학술발표회 논문집 · 2006
To improve indoor air quality, kitchen hood and exhaust fan for the restroom were operated in the new apartment house. Air flow rate at each room was measured while they were operating. The constant concentration was conducted during experimental process and the concentration of the tracer gas was measured with a gas monitor. There were two buildings that air flow measured in. The result was that one was 1.2 ACH and the other was 1.0 ACH. Moreover, it was measured indoor concentration while exhaust system was operating in the apartment. HCHO and toluene were diminished 33% and 43% with respect for 10 days.