터보냉동기용 만액식 증발기 성능해석
김내현, 정진희, 김익생 · 대한설비공학회 학술발표대회논문집 · 1997
A computer program which simulates flooded refrigeration evaporations(FRE) is developed. The program incorporates theoretical models to predict the refrigerant shell-side boiling heat transfer coeffient and pressure drop across the tube bundle. The program adopts an incremental iterative procedure to perform row-by-row calculations over specified incremental tube lengths for each water-side pass. The program was used to simulate the FRE of T company operating with R-123, which yielded satisfactory results. The program was extended to predict the performance of FRE operating with R-11 and R-134a. The effects of bundle aspect ratio are provided.
Cited by 0 works.