퍼지 알고리즘을 이용한 시스템 에어컨의 냉매충전량 감지 프로그램 개발
태상진, 최창식, 김훈모 et al. · 설비공학논문집 · 2006
This study developed a program for detecting charged refrigerant amount in system air-conditioner. System air-conditioner is an air-conditioning system with multiple indoor units. Due to the complexity of the system, it is more difficult to detect the refrigerant amount charged in the system air-conditioner than in a general single air-conditioner. Experiments were performed for a 6 HP outdoor unit with 3 indoor units in a psychrometric calorimeter. The experimental amount of the charged refrigerant was ranged from 60% to 140% with 10% increasement. Fuzzy algorithm was employed for detecting the charged refrigerant amount in the system air-conditioner. The experimental data were used for curve-fitting for the general ranges of indoor and outdoor temperature conditions. Membership function was determined for the whole ranges of experimentally measured data and rule-bases were defined for each charged refrigerant amount. Developed program successfully predicted the measured data within 10% resolution range.
Cited by 0 works.