물분무노즐의 분사각이 화재실 내부의 온도장에 미치는 영향

김성찬, 유홍선, 박현태 et al. · 대한기계학회 춘추학술대회 · 2003

The present study investigates the effect of injection angle of water mist on fire suppression characteristics by numerical simulation. In order to validate the temperature field by numerical simulation, the predicted results are compared with experimental data. It shows that the temperature difference between measurements and predictions are within 10 . Numerical simulations of fire suppression are performed for 4 different injection angle(60°, 90°, 120°, and 180°). The grobal mean temperature over the fire compartment decrease with increasing of spray angle. The result shows that the heat transfer between droplets and gas phase are enhaced with the increasing of spray angle. Near the fire source, temperature field by the wide spray angle is slightly higher than that of narrow injection angle because of direct cooling of fire source.

Cited by 0 works.

Authors