겨울철 가습 및 환기에 따른 교실내 쾌적환경 분석
정성일, 성내리, 김두현 et al. · 대한설비공학회 하계학술발표회 논문집 · 2009
In this paper, the effects of ventilation and humidification on thermal comfort and indoor air quality(IAQ) were evaluated in a classroom when a heat pump system was operated in winter. Thermal comfort parameters, such as temperature, relative humidity, globe temperature and air velocity, were measured at 9 points in the classroom. The concentration of CO₂ and total suspended particles(TSP) in the classroom were measured in order to analyze IAQ. Temperature distribution in the classroom was decreased by 2∼5℃ when the ventilation system and the humidifier were operated. When the relative humidity was adjusted to 60% by operating the humidifier and the ventilation system, the predicted mean vote(PMV) in the classroom was within the comfortable range of -0.5~0.5. When the ventilation system was operated, the average concentration of CO₂ and TSP were decreased by 645 ppm and 0.17 mg/㎥, respectively. This paper suggests the humidification and ventilation conditions to maintain the comfortable environment in the school classroom in winter experimentally.
Cited by 0 works.