히트 펌프 냉난방 시스템의 실사용을 통한 경제성 분석

신규원, 김길태, 주호영 et al. · 대한설비공학회 학술발표대회논문집 · 2006

The present study has been conducted economic analysis through actual operation of EHP and GHP which are installed at the same building of an university. Cost items, such as initial cost, annual energy cost and maintenance cost of each system are considered to analyze LCC and economical efficiency is compared. The initial cost is considered on the basis of actual costs, and annual energy cost is converted into the cost after measuring electricity and gas consumption a day. LCC applied present value method is used to assess economical efficiency of both them. Variables used to LCC analysis are electricity cost escalation rate, natural gas cost escalation rate, interest rate, and service lives and when each of them are 4%, 2%, 8%, and 20 years, results of analysis show that EHP(148,257,306 won) is 8.05%(12,981,990 won) more profitable than GHP(161,239,296 won).