관경변화에 따른 탄화수소계 냉매의 증발 열전달 및 압력강하 특성

이광배, 이호생, 김재돌 et al. · 한국마린엔지니어링학회 학술대회 논문집 · 2004

Experimental results for heat transfer characteristic and pressure gradients of HCs refrigerants R-290, R-600a, R-1270 and HCFC refrigerant R-22 during evaporating inside horizontal double pipe heat exchangers are presented. The test sections which has one tube diameter of 12.70mm with 0.86mm wall thickness, another tube diameter of 9.52mm with 0.76mm wall thickness are used for this investigation. The local evaporating heat transfer coefficients of hydrocarbon refrigerants were higher than that of R-22. The average evaporating heat transfer coefficient increased with the increase of the mass flux. It showed the higher values in hydrocarbon refrigerants than R-22. Comparing the heat transfer coefficient of experimental results with that of other correlations, the presented results had a good agreement with most of the Kandlikar's correlations. Hydrocarbon refrigerants have higher pressure drop than R-22 in 12.7mm and 9.52mm. This results form the investigation can be used in the design of heat transfer exchangers using hydrocarbons as the refrigerant for the air-conditioning systems.