수열원 물대물 냉난방시스템의 운전특성 분석
박진훈, 박태진, 조용 · 대한설비공학회 동계학술발표회 논문집 · 2009
The research assesses the performance of the water-to-water heat pump system installed in C water treatment plant for cooling and heating ventilation. The system uses the unused energy which is a natural heat source of 5~25℃ low temperature like river water to supply stably the demand for the cold and warm heat. For 1 year, the performance of the system had been investigated for the temperature of the raw water, used in intake source, which is varied with heat flux from the geological stratum. In summer season monthly averaged COP is ranged from 3.85 to 4.56, and the performance is dropped as the raw water temperature is increased. While, heating performance is dropped at the low raw water temperature, and the monthly averaged COP is changed from 2.92 to 3.82. It is thought that the heat pump system using raw water resources would be more stable if an additional device is installed to increase the temperature of the intake raw water slightly.