물대공기 열펌프 시스템의 성능해석
한도영, 박관준 · 1996
The water-to-air heat pump system requires relatively lower energy consumption and less installation space. The heat exchangers used for this system are the finned-tube type for the indoor unit and the double-tube type for the outdoor unit. Mathematical models for this system were developed and programmed in computer. Experimental data from various conditions were taken and compared with calculated values from the computer simulation program. Differences of cooling capacity and COP were 1.25% and 0.47%, and those of heating capacity and COP were 0.51% and 0.13%, respectively. Simulation results are in good agreement with test results. Therefore, this developed program can effectively be used for the design and the performance prediction of water-to-air heat pump system.
Cited by 0 works.