혼화재 종류 및 섬유 혼입률 변화에 따른 고강도 콘크리트의 내화특성

장기현, 배장춘, 김호림 et al. · 한국건축시공학회 학술.기술논문발표회 논문집 · 2007

This study investigates the fire resistance properties of high strength concrete, around 60MPa class, designed with various admixture types and fiber content. Test showed that the increase of fiber content decreased the fluidity and slightly inclined the air content of fresh concrete. However, the fiber content in concrete did not affect the compressive strength. For the addition of admixture, specimens adding the shrinkage-reducing-agent (SR) indicated the strength value at 70㎫, which is followed by incorporating silica fume (SF) at 66㎫, the combination of expansive admixture (EA) and SR at 63㎫, only EA at 59㎫, blast furnace slag (BS) at 58MPa and fly ash (FA) at 50MPa in an order. After completing the fire test, all specimens adding 0.05vol.% of polypropylene fiber exhibited protection of spalling, except for the specimens incorporating 30% of SF and incorporating 20% of SF with only SR and the combination of EP and SRA, respectively. Therefore the most effective result of this study was shown in the specimens incorporating 30% of FA and 30% of BS and incorporating 20% of SF with 5 % of EA. It is expected that this test results will be crucial references in near future to develope the spalling resistance method of high strengh concrete.