덕트접속공법에 따른 누기량과 처짐강도 비교실험

김용기, 이태원, 박노광 et al. · 대한설비공학회 학술발표대회논문집 · 2001

In recent years energy losses in the duct work of forced air distribution systems have come under intense scrutiny. Energy losses in the duct work are due mainly to air leakage. Air leakage rates in commercial building duct systems are very difficult to measure accurately: however, a synthesis of measurement from a set of light commercial buildings suggests an average leakage rate in supply ducts of approximately 25% of the flow through the supply fan. This paper presents a comparison of duct connection methods by leakage test and depression strength test. CD connection method shows highest performance on leakage prevention and nearly the same results for the depression strength of L shape steel flange connection method by using cross-beading steel and double flange.