공랭식 열교환핀이 부착된 열전모듈의 냉각 성능에 관한 연구
신재훈, 한훈식, Yoon‐Ho Kim et al. · 설비공학논문집 · 2010
Thermal performance of louver fin and plate fin in a thermoelectric cooling system with a duct-flow type fan arrangement is analytically evaluated. The thermoelectric cooling system consists of a thermoelectric module and two heat exchanger fins. The analytic results show that the optimized louver fin has lower thermal resistance than plate fin. The COP and heat absorbed rate of the thermoelectric cooling system with optimized louver fins are 10.3% and 5.8% higher than optimized plate fins, respectively.