건식이중바닥 온수온돌 시스템의 실내온열환경 및 열적특성
최동혁, 김난행, 손장열 · 대한건축학회 학술발표대회 논문집 - 계획계 · 2004
The aim of the research was to evaluate the characteristics of indoor thermal environment related to thermal storage in the two kinds of Ondol heating system. Physical indoor thermal environments (the floor surface temperature, the vertical temperature etc.) and thermal comfort indicators(PMV, PPD, OT) have in particular been measured. (1)As a result of measurement of indoor temperature and relative humidity, it appeared to be 20.4℃ and 33% in case of wet Ondol, 19.2℃ and 27.3% in case of dry double floor Ondol heating system. In case of wet Ondol indoor temperature satisfied 22℃ which is the comfort condition for indoor temperature in winter for 11 hours at 5hours after the starting point of heating and in case of the dry double floor, in door temperature satisfied the comfort condition for 4 hours at 2 hours and 20minutes after the starting point of heating. However, relative humidity didn'tgenerally satisfied comfort condition in both case of wet Ondol and dry double floor.
Cited by 0 works.