An experimental facility consisting of two 3×4.4×3.8m rooms identical in construction is built. Each room had a control system for radiant floor heating system. The facility enables simultaneous comparision of two different control stratigies each implemented in a separate room. The operating performance of three kinds of flow control scheme was tested and compared in this study : (ⅰ) on-off control with feedback of room air temperature controlled by supply water temperature or return water temperature (ⅱ) on-off control without feedback of room air temperature controlled by supply water temperature or return water temperature (ⅲ) multi-step outdoor air temperature compensation control. Results show that multi-step outdoor air temperature compensation control of hot water supply temperature can maintain the room air temperature within the thermal comfortable range and conserve heating energy.