이중외피 적용에 따른 냉난방설비 비용분석 연구
Jung Ho Kim, 이건호, 강기남 et al. · 대한설비공학회 하계학술발표회 논문집 · 2010
This paper analyzes reducing Air-conditions facility costs according to applying Double Facade System to a building. CDFS (Compact Double Facade System) developed by the Korea Institute of Construction Technology was applied to the target building of a specific region. and we calculate the heating and cooling load, choose equipment capacity and analyze the costs in parts of before and after. The results of this study were as follows; (1) When we make a comparison the CDFS between the normal facade system in the load, CDFS saves about 17% in cooling load and about 15% in heating load. (2) Equipment capacity reduction occurs except Package air conditioners and CTCHs, details shown below - AHU has been shown to reduce approximately 5.7% in cooling and 1.6% in heating - FCU appears to reduce about 36.6% in the both capacity and the saving rate was the largest in the equipments - EHP was about 7.1% in the both of it. (3) Facilities construction costs need about ₩1,610 million in case of the normal facade system and ₩1,538 million in case of the CFDS, save ₩72 million (4.5%) by applying CDFS
Cited by 0 works.