아파트 단위주거 리모델링후 실내공기질 실태
최윤정, 심현숙 · 대한건축학회 학술발표대회 논문집 - 계획계 · 2007
The purpose of this study was to grasp the present condition of indoor air quality after remodeling in apartment units. Field measurements were carried out in 20 apartment units recently remodeled, the methods were measurement on the indoor factors(CO2, CO, PM10, TVOC, HCHO), investment on remodeling contents by resident's interview and influencing factors by researcher's observation. As results, the averages of CO2 in each house were 683~2309 ppm, the number of houses exceeded the Standard(1000 ppm) were 14. The averages of CO in each house were 0.2~6.1 ppm, all houses were kept within the Standard(10 ppm). The averages of PM10 in each house were 0.8-74.8 ㎍/㎥, all houses were lower than the Standard(100 ㎍/㎥). The averages of TVOC in each house were 0~0.3 ppm, the number of houses exceeded the Standard(0.1 ppm) for the Occupied building were 11 and 6 houses were higher than Standard(0.58 ppm) for the New-built apartment. The averages of HCHO in each house were 0~1.0 ppm, the number of houses exceeded the Standard(0.1 ppm) for the Occupied building were 12, and 10 houses were higher than Standard(0.17 ppm) for the New-built apartment.