중성점 접지 리액터 주변 작업자의 인체내부 유도전류밀도 특성
민석원, 이승호 · 2010
To reduce a high fault current, neutral ground reactors (NGR) were installed in the Korean substation. Current with several harmonic components flows in a NGR due to load unbalance in normal steady state and magnetic fields with several harmonic components are also generated around a NGR. As results of study, we found magnetic fields around a NGR in Korean substation included two harmonics, 180㎐ and 540㎐. Magnetic fields of 180 ㎐ increased 3 times more current density inside a worker near a NGR than same magnitude magnetic fields of 60 ㎐. We know a worker near a NGR may not meet ICNIRP guideline of 10(㎃/㎡) due to several harmonic components.
Cited by 0 works.