디더 신호를 적용한 멀티형 히트펌프의 전자팽창밸브 과열도 제어

한도영, 표수환 · 대한설비공학회 학술발표대회논문집 · 2001

The electronic expansion valve(EXV) may be used to control the refrigerant flow rate for the multi-type heat pump. EXV using a stepping motor may precisely control the refrigerant flow rate to meet each internal load requirement. To control the EXV, PI algorithm may be used. But the hysteresis of EXV deteriorates the performance of superheat temperature control. To reduce the performance degradation, a PI controller along with the dither signal, whose frequency is higher than the system crossover frequency, may be used. For the superheat temperature control of EXV, dither signals were used. Test results show the effectiveness of the dither signal added to the PI algorithm.

Cited by 0 works.