자연환기 벤틸레이터 환기유량 산정
하현철, Tae Hyong Kim, 정계수 · 대한설비공학회 하계학술발표회 논문집 · 2002
As a natural ventilation strategy, general gravity ventilators can be installed on the roof of an industrial building. Unfortunately, the appropriate design data for this type of ventilator could not be found except for the design data in commercial catalogues in which there is no scientific reference. In this study, the ventilation rates of gravity ventilator were thus evaluated for the several design parameters, i.e. 1) wind direction, 2) wind speed, 3) temperature differences between the exterior and interior of a building and 4) ventilator height and width. A commercially available CFD (Computational Fluid Dynamics) package was used to estimate the ventilation rates numerically. The ventilation performance were enhanced as 1) the wind direction is close to the perpendicular direction of industrial building, 2) wind speed increases, 3) the temperature difference between the exterior and interior of a building increases, and 4) the width of ventilator neck enlarges. In addition, the temperature difference is the dominant factor in the lower wind speed (0~2.5㎧) while the wind speed act as significant factor in the higher wind speed (2.5~10㎧). The flow rate of low height ventilator is dramatically reduced than standard height. But efficiency of tall ventilator aimed for increasing flow rate was insignificant.
Cited by 0 works.