내부 그루브를 갖는 전열 촉진관의 성능 해석 연구

조홍기, Taeheon Kim, 홍순철 et al. · 대한설비공학회 2013년도 하계학술발표대회 · 2013

The objective of present work is to investigate the performance of enhanced tubes with inner grooves by using a commercial CFD program. Four different enhanced tubes have been studied. G_0 and G_max tubes have no inner grooves on their inner surfaces, therefore, their inner surfaces are smooth. The inner diameter of G_0 and G_max are 8.9 mm and 9.9 mm, respectively. G_6 has 6 inner grooves and G_12 has 12 inner grooves. For all enhanced tubes, Serrated fins are manufactured on their outside surfaces and the inner groove is 1.0mm in width and 0.5mm in depth. As the number of inner grooves increase from 0 to 6 and 12, the pressure drops for G_6 and G_12 increased by 18% and 20% and the heat transfer rates increased by 7% and 14% under the mass flow rate of 189 kg/hr. In case of G_max, pressure drop and heat transfer rate decreased by 29% and 6% than those of G_0, because G_max have no inner grooves and its diameter is larger than that of G_0 by 1.0 mm.