터보 냉동기의 효율 개선 방안
김기태, 김한영, 장시혁 et al. · 대한설비공학회 동계학술발표회 논문집 · 2012
Recent CFD studies for predicting the performance of a centrifugal-chiller is active. In this study, the method to minimize a loss of impeller and diffuser has been investigated with an one-dimensional analysis of COMPAL. After understanding the one-dimensional internal flow characteristics changing geometry such as inlet/outlet blade angle of impeller and diffuser, we studied the trend of pressure and loss change according to the geometry changes. In the result of a three-dimensional analysis using the feature of geometry, we have approached a designed goal, and a development time has been shortened.