축사용 폐열회수 환기장치의 열교환소자 설계를 위한 수치해석적 연구

한화택, 남상훈, 한건수 · 대한설비공학회 동계학술발표회 논문집 · 2010

A numerical study on heat exchanger element is presented to design high efficiency HRV units for livestock buildings. Since it is humid in livestock buildings, condensation and frost formation can create problems and decrease heat exchanger performance. In this study, the heat exchanger efficiency and pressure loss are evaluated by varying flow rates and outdoor temperature conditions. The condensation area and frost area are evaluated from psychrometric analysis to ensure proper airflow rates through the exchanger. Results show that the efficiency decreases and pressure drop increases with flow rate increased. The condensation area is increased with flow rate increased at -5℃ and -10℃, but it decreases with flow rate changes 10 to 15 CMH at -20℃.

Cited by 0 works.