냉매충전량이 초임계 이산화탄소 사이클의 냉방성능에 미치는 영향에 대한 연구

조홍현, 류창기, 김용찬 et al. · 설비공학논문집 · 2005

The cooling performance of a transcritical CO₂ cycle varies significantly with a variation of refrigerant charge amount. In this study, the performance of the CO₂ system was measured and analyzed by varying refrigerant charge amount at a standard test condition. Besides, the losses of the major components in the CO₂ system were estimated by evaluating entropy generation with refrigerant charge amount. The losses in the expansion device and the gascooler show the major portion of the total loss. For undercharging conditions, the expansion loss dominates the overall system performance, while the gascooler loss increases significantly with an increase of refrigerant charge amount.

Cited by 0 works.

Authors