HTS fault current limiter concept
Swarn Singh Kalsi, A. P. Malozemoff · IEEE Power Engineering Society General Meeting · 2004
Fault current limiter (FCL) concepts based on non-inductive high temperature superconducting (HTS) coils were studied. The coils employed second generation (2G) HTS wire based on YBCO coated conductor currently under development at American superconductor corporation (AMSC) and other places. Two FCL concepts were studied: a) series and b) shunt. The series limiter employs a coil in series with the load and limits current by its increased resistance during the current limiting phase. This design is best for a single fault current limiting action, with resetting after the several minutes required cooling it down to its prefault temperature. The shunt limiter employs an inductor in parallel with the HTS coils. Once the HTS coil transitions to its normal state, fault current is limited by the impedance of the external inductor. An advantage of the shunt limiter is that with proper design, it could withstand multiple closely timed current limiting events. Since the 2G wire is becoming available in long lengths, now is the right time to initiate a commercial FCL product development program.
Cited by 81 works. doi:10.1109/pes.2004.1373103
Authors
References
- Towards the superconducting fault current limiter
- Comparison of superconducting fault limiter concepts in electric utility applications
- 6.6 kV/1.5 kA-class superconducting fault current limiter development
- Hybrid superconducting AC fault current limiter principle and previous studies
- Practical neutral-axis conductor geometries for coated conductor composite wire
- Testing of a 1.25-m HTS Cable Made from YBCO Tapes