반도체 클린룸용 외기공조시스템의 에너지소비량 분석 실험

김형태, 송근수, 유경훈 et al. · 대한설비공학회 학술발표대회논문집 · 2010

In recent semiconductor manufacturing clean rooms, the energy consumption of outdoor air conditioning systems represents about 45 % of the total air conditioning load required to maintain a clean room environment. Therefore, the performance evaluation of outdoor air conditioning systems is useful for reducing the outdoor air conditioning load for a clean room. In the present study, an experiment was conducted to compare the energy consumption of steam humidification, water spray humidification, exhaust-air heat-recovery and DCC(dry cooling coil)-return-water heat-recovery outdoor air conditioning systems. It was shown from the lab-scale experiment with an outdoor air flow of 1,000 ㎥/h that the DCC-return-water heat-recovery outdoor air conditioning system was the most energy-efficient for the wintertime operation.

Cited by 0 works.