히트펌프 핀-관 증발기 핀 개수에 따른 서리 특성

곽동근, 김승연, 조금남 et al. · 대한기계학회 춘추학술대회 · 2010

The present study investigated frost characteristics of fin-tube evaporator with multiple fins for the heat pump. Number of fin was ranged from one to five. Key test conditions were air temperature of 2℃, absolute humidity of air of 3.7g/㎏DA, air velocity of 0.5㎧, and surface temperature of the refrigerant of -10℃. The coolant was 50% ethylene-glycol aqueous solution. Local and average frost thicknesses were measured around the fin of the fin-tube. They were compared with the values predicted by the correlations obtained as the function of frost temperature for the flat plate and circular tube. Average frost mass was gradually increased as the number of fin increased even though frost characteristics for the case with multiple fin showed similar trend with the case with single fin through the test period. Similar frost pattern was observed at different gap between adjacent fins. The effect of number of fins on the frost characteristics was analyzed.

Cited by 0 works.

Authors