폐열회수 환기장치의 온동효율 개선에 관한 연구

정영권, 김재정, 김영수 et al. · 한국마린엔지니어링학회 학술대회 논문집 · 2006

To improve the temperature efficiency, a newly designed Energy Recovery Ventilator(ERV) with conductive guide vane is experimented and verified. The experimented pilot system is designed base on various CFD analyses.(flow, heat transfer) The developed pilot system, 250 CMH capacity, reveal temperature efficiency improvement of 6.14% in cooling period and 8.07% in heating period compared to the conventional ERV. These improved efficiencies mean 'supply air' temperature is lower 0.49℃ in cooling period and higher 1.21℃ in heating period than ERV without conductive guide vane.

Cited by 0 works.

Authors