병렬펄스부하를 갖는 직류배전시스템을 위한 능동 공진 댐퍼에 대한 연구

나재두, 이병헌, 장한솔 et al. · 2012

An active resonance damper for a DC Distributed Power System(DPS) with parallel loads is presented. Each pulse power load in a DC DPS comprises both a resistive power load and a step-up converter. The step-up converter behave as constant power load(CPL) when tightly regulated and usually cause a negative impedance instability problem. Furthermore, when an input filter is connected to a large constant power load, the instability of DC bus voltage. In this paper, a bidirectional DC/DC converter with a reduced storage capacitor quantitatively are proposed as a active resonance damper, to mitigate the voltage instability on the bus. The validity of the proposed method was confirmed by simulation and experimental works.

Cited by 0 works.