학교 교실의 태양광발전 환기시스템 적용성 연구
장용성, 서승직, 홍성희 et al. · Journal of the Korean Solar Energy Society · 2005
This study aims to evaluate application of a heat recovery ventilator (HRV) using photovoltaic (PV) system. To this end, we analyzed performance of a PV system, which it was evaluated by monthly power wattage and conversion efficiency accrording to design capacity of a HRV. The results of this study can be summarized as follows. (1) A conversion efficiency of the PCS was evaluated about 86% in rated power. (2) A maximum, minimum and average output power were respectively analyzed 49.2W, 47.3W, and 48.8W. (3) Total power wattage of 200W PV system was 211kW and it was 316kW in case of 300W PV system. (4) Insufficient electrical power of a duct and window type ventilation system was respectively calculated 133.5kW and 147.7kW.