백연 방지를 위한 NWD 냉각탑의 성능해석에 관한 수치해석적 연구

최창경, YoungKiChoi, 소헌영 · 2001

The performance and design analysis for a NWD cooling tower using a combined wet and dry type fill are numerically investigated and compared with the experimental results. The Stoecker's method is applied to the wet section and LMTD or NTU-Effectiveness method to the wet and dry sections. The efficiency ratio of the NWD cooling tower to a wet type crossflow cooling tower is 59.34%. The predicted result shows a good agreement with the experimental data within 1.4% error. Plume abatement is far better with a NWD cooling tower than a counterflow cooling tower. It costs less than a conventional wet/dry tower because the finned exchanger is eliminated. This method also leaves out complexity in structure and intricacy in operation.

Cited by 0 works.