위험전압 측정시스템의 설계 및 제작

장운용, 김선재, 차현규 et al. · 한국철도학회 학술발표대회논문집 · 2010

This paper dealt with the design and fabrication of a Risk Voltage Measurement System(RVMS) which analyzes a step and a touch voltage of electrical ground systems. The RVMS produces sine-wave voltage up to 300 Vrms in ranges of 40 Hz ~ 1 kHz. An analog to digital(A/D) converter with 400 kS/s and 16 bit, is applied to measure the step and the touch voltage. A digital band-pass filter is applied to minimize measurement error by external noise. Field test was carried out in a ground system which is composed of underground-wiring electrode.

Cited by 0 works.