배전계통의 보호기기 동작시간을 고려한 초전도 전류제한기의 임피던스 제한방안

김진석, 김명후, 유일경 et al. · 대한전기학회 학술대회 논문집 · 2010

In this paper, the selection method of the pickup current multiples in the over-current relay with a superconducting fault current limiter (SFCL) is proposed to keep the protection coordination between a recloser (R/C) and a circuit breaker (CB). Immediately after the fault occurs, the fault current can be limited by SFCL and, if the fault continues, the fault current is interrupted by a R/C and a CB after several cycles. Those operations are decided by each time-current curve (TCC), and the operations have to maintain the operation time interval between two protection devices the for the protection coordination. However, the interruption time of the R/C and CB delays because the fault current is reduced by the impedance generation of the SFCL when a fault happens. Although higher impedance of the SFCL is more effective on the current limit, the delay operation due to the limited fault current can result in the failure of the protection coordination in the protection devices.