공냉식 방사형 열교환기를 갖는 흡착식 히트펌프의 성능

백남춘, 양윤섭, 윤응상 et al. · 1997

In this experimental study, the air cooling radial shape heat exchanger which influences on the COP and the cooling capacity by heat and mass transfer rate in the adsorbent bed was designed and applied to test its performance for adsorption heat pump(AHP). Zeolite-water was used for the adsorbent-adsorbat pair. As a result, the cooling COP and a cycle period of this adsorption heat pump are 0.28 and 2 hours, respectively, on the condition of none heat recovery from the adsorption reactor(absorber). The other results and recommendations are mainly related to improving the heat and mass transfer inside the absorber to reduce a cycle period.

Cited by 0 works.

Authors