설비형 칠드빔 시스템의 실온 및 결로 제어성능에 관한 실험적 연구

이규남, 최선호, 김창훈 · 대한건축학회 학술발표대회 논문집 · 2014

Diverse studies have been conducted on design parameters to obtain proper cooling capacity, and thermal comfort under design conditions. However, those studies mainly focused on the performance of chilled beams under specific conditions, thus it is difficult to investigate the performance under dynamic load change, which is frequently observed in the building operations. Therefore, this study aims at investigating the suitable parameter for controlling room air temperature and preventing condensation on water pipe, assuming a dynamic load change in the mock-up test room. The result showed that the primary air flow rate is a suitable parameter for room air temperature recovery and condensation prevention under dynamic load change