핀-관 열교환기의 응축수 비산 특성에 관한 실험적 연구

이수원, 안승표, 문정욱 et al. · 대한설비공학회 하계학술발표회 논문집 · 2001

The present experimental study was investigated the carry-over velocity of finned tube evaporator. The carry-over velocity was effected by surface characteristics. To measure inlet air velocity of indoor unit laser doppler anemometer(LDA) was used. The results showed that the carry-over velocity of partially wetted evaporators were lower than fully wetted ones. To avoid carry-over in the air conditioner having the highest air velocity of 1.5 m/sec, the dynamic contact angle(DCA) should be at least lower than 60˚.