원전공조용 열교환기의 핀 형상에 따른 성능 변화
배성원, 김정훈, 김무환 et al. · 대한설비공학회 학술발표대회논문집 · 1997
In this study, air cooling heat exchangers with the helical and plate fin are tested in the way of ARI Standard-410. The configuration of the heat exchanger is cross flow. The helical fin shaped heat exchanger have 6, 8 and 10 fin per inch. And plate fin shaped heat exchanger has only 8 fin per inch in this study. The experimental parameters are front air velocity and in-tube water velocity. The front air velocity varys from 1 m/s to 4m/s with 1m/s increment and in-tube water velocity has two steps that are 0.5m/s and 2.2 m/s. As the results, the helical shaped heat exchanger shows better heat transfer coefficient. For helical fin shaped heat exchangers, the performance variation is little, but 10 fin per inch heat exchanger shows greatest performance when considered both the heat transfer area and heat transfer coefficient.
Cited by 1 works.