공조용 풍량측정 오리피스의 최적위치
이승철, 안재성, 이재헌 · 2000
In this study, five experiments were carried out, with an orifice located downstream of a fan in case I and different downstream distance to the fan in the rest, so as to determine the optimal location of the orifice and reduce the size of airflow measurement device. The resulting flow rate-pressure drop correlations were found to satisfy the limitation of SMACNA standard, which specified an error of ±7.5% based on the real flow rate. The best outcome was achieved with the orifice located midway of the orifice duct 4 times its diameter long.
Cited by 0 works.