업무용 건물 중앙공조 및 개별냉난방 시스템 연계운전방안

권한솔, 김용기, 이태원 · 대한설비공학회 2013년도 하계학술발표대회 · 2013

The daily electric energy consumption of the electrical heat pump(EHP) was investigated, and the heating coefficient of performance(COP) during winter season was analyzed in the present study. The optimal combination strategies of heating systems, which were composed of individual EHP’s and centralized gas boiler, were also determined in a medium sized domestic office building. It was found that the daily heating COP of EHP was lower than the given data by the producer especially in the region of relatively high outdoor air temperature. The optimal combination of operation strategies were proposed for the two types of heating systems installed in this testing building.