태양열 이용 냉난방 공조시스템 중 전열교환기의 최적운전조건에 관한 연구
김형철, 김보철, 김광호 et al. · 대한설비공학회 학술발표대회논문집 · 1999
The experiment on dehumidification performance of a solar air-conditioning system was designed, done and analyzed by the design of experiment. Using the table of orthogonal arrays L_8(2^7) the analysis of variance was done. According to the results, most influential factor on dehumidification rate was concentration of LiCl solution. The next influential factors were temperature of LiCl solution, air flow rate. The factors of packed layer height, packed material, and flow rate of LiCl solution had no influence on dehumidification performance in these experimental conditions. Through the three level experiments of L_(27)(3¹³), it was found that the optimal combination of factors was A₂B_0G₂(concentration of solution 30 wt%, temperature of solution 15℃, air flow rate 253㎡/h).