초고층 건물에서 로비의 형상과 창 면적비에 따른 연돌효과 평가

유정연, 조동우, 유기형 et al. · 대한건축학회 추계학술발표대회 논문집(계획계) · 2004

Buoyancy forces due to the air density differences between outdoor air and indoor air cause stack effect in high-rise buildings in cold climates. In addition to, the lobby of typical high-rise building takes the shape of an un-insinuated atrium. The airflow of this open space of the lobby increases stack effect in winter and the large windows of the hall rise cooling loads in summer and heating loads in winter. For the evaluation of stack effect according to the shape and the window area ratios of the lobby in high-rise buildings, computer simulations based on network model are performed. Building design guidelines are proposed as results from it. The results of the simulations are verified with field measurements.