핀 형상에 따른 열교환기 성능 비교
맹재훈, 구병수, 전용두 et al. · 대한설비공학회 동계학술발표회 논문집 · 2010
Fin tube heat exchangers have been used in many industrial applications. In the waste heat recovery applications, however, the selection of high performance fin shapes are challenged by the adverse operating conditions as high humidity and fouling sources. In this study, the heat recovery performance of different fin shapes (plain, spiral, twist, curved wavy) are experimentally studied in terms of the j-factor and the associated f-factor. For this study the water inlet temperature was set to 60℃(±1) while the gas inlet temperature ranged from 125~140℃ depending on the flow rates that correspond to the Reynolds number(R eD, m ) from 5,313∼8,008. According to the tested results, the wavy fins(6 fins/inch) showed the superior performance in terms of j/f factor, although the twist fins showed the highest j-factor, and the spiral fins(8 fins/inch) showed the highest f-factor. Among the test fins, the spiral fins(8 fin/ inch) showed the lowest values in j/f ratio and the wavy fins showed the highst j/f-factor ratio.