일사를 고려한 페리미터 공조시스템의 열성능 비교평가
함흥돈, 백용규, 손장열 · 한국생활환경학회지 · 2005
For the purpose of investigating the effective removal of cooling load from light-weighted building envelope, two air-conditioning systems, conventional all-air and air-barrier system, are evaluated and compared by both experiment and simulation with three different cases during cooling season. The characteristics of window-side building thermal load are assessed by varying supply air velocity in order to seek the optimal system operation condition. The results are as follows. Air-barrier system is more effective to remove solar radiation through glass at perimeter zone than conventional all-air system. The experiment results provide that capturing efficiency to evaluate the effective removal of building load from perimeter zone shows high value when supply air velocity is 1 ㎧.