시송전계통의 고조파 공진현상에 대한 분석
李興載, 李坰燮 · 전기학회논문지 A · 2006
Power system restoration following a wide area or complete blackout starts with energizing primary restorative transmission systems. During this primary restoration process, unexpected over-voltage may happen due to nonlinear interaction between the unloaded transformer and the transmission system. This is known as the harmonic resonance phenomenon that may cause burning out of transformer or other devices. Since the harmonic resonance originates from the nonlinear characteristics, it is very difficult to predict the occurrence of this phenomenon. This paper reports the analyses of the harmonic resonance occurred in domestic power system. Various analyses and results of the harmonic over-voltage is presented based on the PSCAD/EMTDC simulations.
Cited by 0 works.