온천 배수 열회수용 히트펌프시스템 적용 사례
김종률 · 대한설비공학회 학술발표대회논문집 · 2009
A spa resort can be treated as one of the most favorite facilities to relax or to have special experience but it can be regarded as one of the most water-spent facilities considering energy saving or energy cost. In this paper, a heat pump system will be introduced as a heat recovery system, which recovers heat out of wasted water from a spa resort. Generally temperature of wasted water from a spa resort is a key factor to consider a heat recovery system design. Temperature of the spa resort studied measured 29 ℃ and quality of wasted water was under 5 ppm. These running conditions made the facility install simpler heat recovery system. As a result, the heat recovery system suggested has produced 2,983,925 Mcal during Winter and 419,084 Mcal(138,586 RTh) during Summer after installation. These results have saved over 240 ton of LPG and yielded 135 million Won savings a year.