창원지역의 지중온도 예측에 관한 연구
조성우, 임병찬 · 설비공학논문집 · 2014
For an analysis of the horizontal-type geothermal heat exchanger system, an understanding of the ground temperature distributions is required in order to predict system performance. Because it is difficult to decide on the underground temperature due to the adjustment of its temperature cycle, numerous calculations are required in order to decide on the temperature cycle. In this paper, Buggs formula is utilized to decide a phase shift for outdoor temperature and ground surface temperature, which are obtained from Korea Meteorological Administration. Overall, the underground temperature distribution in the Changwon region is predicted as 10.5℃~20.3℃ at a depth of 3 m.
Cited by 0 works.