태양열 냉방 실증시스템의 난방 및 급탕 열성능
곽희열, 주홍진 · 한국태양에너지학회 춘계학술발표회 논문집 · 2007
This study describes thermal performance of heating and cooling demonstration system using ETSC(Evacuated tubular solar collector) installed at Seo-gu art center of Kwangju. For demonstration study, a reading room with about 350㎡ was heated and cooled using that system. The demonstration system was consisted of ETSCs, storage tank, hot water supply tank, subsidiary boiler, and subsidiary tank. The results of the experimental study From January to February in 2007, The solar fraction were 58% for solar heating, 30% for solar hot water in January and 79% for solar heating, 33% for solar hot water in February.