지열히트펌프의 성능 확인을 위한 실험적 연구 및 냉방 에너지 분석에 관한 연구

장재철, Ji-Young Kim, 박성룡 et al. · 대한설비공학회 하계학술발표회 논문집 · 2011

This study is about commissioning of GSHP(Ground Source Heat Pump) based on ISO standard performance data. Initial performance was low, so replaced expansion device. Enhanced GSHP was compared to the performance of cooling energy by used TRNSYS. As a result, cooling energy was increased about 7.2% by commissioning procedure and amount of consumption power was reduced about 3.6% while cooling period.

Cited by 0 works.