절연유에서 부분방전에 의한 극초단파 신호 특성분석

朱炯俊, 具嬋根, 朴基濬 et al. · 전기학회논문지 P · 2008

We have designed 4 types(void in insulation paper, protrusion electrode, floating electrode, surface discharge) of partial discharge(PD) defect to simulate typical faults found in oil filled power transformers Ultra-high frequency(UHF) radiation due to PD was measured using a UHF measuring system and a conventional PD measuring system, simultaneously. Electromagnetic radiation spectra of these defects show UHF radiation up to about 1.5-2 ㎓ range. The phase resolved partial discharge(PRPD) patterns of UHF radiation from the PD defects were also measured and the pattern reveals distinct feature for each defect types. The UHF measuring could be used to detect PDs in oil filled transformers and analysis of the PRPD pattern should provide useful information on origin of PD signal.

Cited by 1 works.