Double CFT기둥의 내화성능에 대한 실험적 연구

송경철, 방중석, 박수희 et al. · 대한건축학회 학술발표대회 논문집 - 구조계 · 2009

Although an unprotected CFT column with a high axial-load ratio can be used to secure fire resistance for two hours or less in low-rise buildings, it does not satisfy the three-hour-long fire resistance required in high-rise buildings. Accordingly, so that the unprotected CFT column could be used for high-rise buildings, additional measures for the improvement of its fire resistance should be suggested. In this regard, the use of a CFDST (Concrete-filled Double Skin Tubular) column as a measure for improving the fire resistance of the unprotected CFT column was suggested in this paper. A fire resistance test was conducted on an unprotected CFT column and a CFDST column in real scale, under a load. Through such test, the effect of the CFDST column on fire resistance was evaluated and then compared with that of a variant shape of the cross-section of a steel column.

Cited by 0 works.