지중열원 열펌프시스템의 성능해석

이세균, 우정선, 노정근 · Journal of the Korean Solar Energy Society · 2005

The performance of water-to-water heat pump system coupled with the ground source vertical heat exchanger is presented in this paper. The CAP program of Florida Heat Pump Co. is used to predict the heat pump performances while the EED program calculates the borehole fluid temperature. It is shown that COPH increases with decreasing the temperature of output water for the operation of heating mode and COPR increases with increasing temperature of output water for the operation of cooling mode. The value of specific heat extraction rate must be moderate to insure the reasonable installation cost of borehole system. With 1℃ decrease of Two the average COPH increase is estimated as about 0.06/℃(for Two=45~60℃ range) while with 1℃ increase of Two the estimation of COPR increase is about 0.13/℃(for Two=5~11℃ range) at the specific heat extraction rate of 30W/m.

Cited by 0 works.